Water distribution system WDS analysis plays an essential role in calibration, design, management, and rehabilitation of pipe networks Head loss calculation, as an important component of pipe network analysis, can be conducted via Darcy Weisbach D W , Hazen Williams, Chezy, and Manning equations The D W equation is the most accurate head loss equation since unlike other resistance equations, it not only satisfies the principle of dimensional homogeneity, but also varies with pipe flow dynamics Although the Colebrook White formula is an accepted head loss equation, it is implicit and consequently considered to be inefficient and cost effective in WDS analysis In order to address appropriate selectionof resistance equation, the literature is filled up with many explicit approximate equations for which the potential user might wonder which equation to use for a certain condition In this paper, the applicability of forty five explicit equations was compared by solving two test networks using the finite element method as solver The results show that not only some of these equations are not reliable in WDS analysis but also they may cause converge problems In light of the results obtained, a few appropriate resistance equations were identified to capture the dynamics of flow in an efficient way